Fire Testing
Circuit Integrity
1. Circuit (insulation) Integrity in accordance with IEC 60331
IEC 60331 specifies tests for electric cable for circuit integrity under fire conditions. It is divided in following
parts that describe the test modes, the conditions, and the equipment to use. The test was originally carried out
only in fire alone for a period of 180 minutes at a temperature of 750°C. To better simulate the real fire
conditions, with mechanical stresses due to the fall of materials and with the presence of water, the testing
conditions have been modified by changing the duration, increasing the temperature of the flame and by adding
mechanical stresses and water spray.
IEC 60331-1 ed 1.0 (2009-05)- Part 1: Test method for fire with shock at a temperature of at least 830°C for
cables of rated voltage up to and including 0.6/1KV and with an overall diameter exceeding 20mm.
IEC 60331-2 ed 1.0 (2009-05)- Part 2: Test method for fire with shock at a temperature of at least 830°C for
cables of rated voltage up to and including 0.6/1KV and with an overall diameter not exceeding 20mm.
IEC 60331-3 ed 1.0 (2009-05)- Part 3: Test method for fire with shock at a temperature of at least 830°C for
cables of rated voltage up to and including 0.6/1KV tested in a metal enclosure.
IEC 60331-11 ed1.01 Consol. with am1 (2009-07) – Part 11: Apparatus – Fire alone at a flame temperature of
at least 750°C.
IEC 60331-12 ed1.01 Consol. with am1 (2009-07) – Part 12: Apparatus – Fire with shock at a flame temperature
of at least 830°C.
IEC 60331-21 ed1.0 (1999-04) – Part 21: Procedures and requirements – Cables of rated voltage up to and
including 0.6/1KV.
IEC 60331-23 ed1.0 (1999-04) – Part 23: Procedures and requirements – Electric Data Cables.IEC 60331-25
ed1.0 (1999-04) – Part 25: Procedures and requirements – Optic Fiber Cables.
IEC 60331-31 ed1.0 (1999-04) – Part 31: Tests for electric cables for fire conditions and shock- Circuit integrity.
Procedures and requirements for fire with shock – Cables of rated voltage up to and including 0.6/1KV.
IEC 60331-21/60331-23 A sample of the cable length of 1200mm sustained by two metal rings is mounted
horizontally in a special ventilated cabin. During the test, to the wire cores of cable a voltage of the nominal
value is applied (for telecommunication cables equal to 110 V), thereby creating a closed electric circuit. The
sample is subjected to an action of linear gas burner with a length of 500mm and the flame temperature equal
to 750°C till 800°C. The time of the fire is 180 minutes. Result of the test is considered positive if at that time will
not be considered a short circuit in the circuit being researched.
IEC 60331-25 details a method to assess the circuit integrity of optical fiber cables. The standard specifies a
ribbon burner and the recommended flame temperature is 750°C. The optical power meter is zeroed and the
changes in attenuation during the 180 minutes burner application period are monitored. The maximum change in
attenuation (a change from zero) is recorded during the burner application period. In the 15 minutes period
after the flame application, a maximum attenuation is also recorded. Result of the test is considered positive if at
that time will not be considered a short circuit in the circuit being tested.
IEC 60331-31 applies to the cables with a diameter greater than 20mm, and introduces the standards nd
procedures for testing of cables exposed to fire and mechanical shock (equipment according to 60331-2). The
test sample provides cable fragment length at least 1500mm. Bent wire on the U-shaped with a adius equal to
the smallest permissible by the manufacturer, is mounted on a metal assay ladder. During the study, through all
the cable wires is passed current with rated voltage and these cables are subjected to fire during 120min,
where fire source is a gas burner set in conformity with standards, as well the echanical shock of the 5 minutes
interval. Result of the test is considered positive if at that time will not e considered a short circuit in the circuit
being tested.